Services We Offer
CABLE COMPARTMENT AND INSTALLATIONS
Do primary test on CT’s and if suspect do magnetizing curves to check
CT saturation.
Check for loose LV connections on CT’s and do a doctor test to check HV
Contacts. Do inspection on cable terminations for telltale signs on heatshrink .
Check for discoloration and weeping on termination end and arcing in
Termination crotch.
SUPPLY USED SWITCHGEAR
Refurbished switchgear at a lower cost quicker deliveries. Any protection
and CT ratio’s can be fitted on these panels.
DUCTOR TEST
Injecting a 100 A DC across contact points to measure the resistance
between two contact points.
OPEN GAP
Earth one side of CB contact and inject 2X the rated voltage on the
other side with the CB open.
PRESSURE TEST
Injecting 2X voltage rating into the switchgear to check insulation
Levels between phases and earth and phase to phase
Installation and commissioning
We will handle your total installation and commissioning requirements.
This service is offered to original equipment manufacturers and where
clients purchase equipment from various manufacturers. Our
expertise extends to the installation and commissioning of the
following :
Medium and Low Voltage Equipm ent & Cables
¬ Indoor and outdoor switchgear
¬ Switchgear retrofitting
¬ Power cables and control cables
¬ Motor control centers
¬ Transformers
¬ Control panels / desksRelay protection panel
Installation of Joints + Termination on medium and low Voltages
Pressure testing of cables